CP1L-E Built-in Analog Input Setup

Updated March 19, 2025

Introduction

The CP1L-EL/EM CPU Units are equipped with 2 built-in analog inputs. When a voltage of 0 to 10 V is applied to the built-in analog input terminal, the voltage is converted from analog to digital and the PV in A642 and A643 can be changed to any value within a range of 0 to 1000

 

 
 

Specifications

Item Specification
Input signal range Voltage input (0V to 10V)
Max. rated input 15V
External input impedance 100kΩ min.
Resolution 1/1000 (so 0V-10V is scaled 0-1000)
Overall accuracy

at 25°C: ±2.0%

otherwise ±3.0% (full scale)

Conversion time Same as the PLC cycle time
Isolation method none
 
 

Analog Input Terminals

Note: PV stands for Present Value, which is the same as the current value based on the Voltage input.

 
 

CX-Programmer Example

Above we can see the Symbols that have been setup for scaling the Analog Input. We also have predefined Symbols for storing the scaled value for V1 and V2

 

Above is the program that will read the Analog Input from the predefined registers (V1: A642 and V2: A643) and output a percentage from 0% to 100%.

Attached below is a copy of the program, note that this program is not supported so use at your own discretion

https://static.helpjuice.com/helpjuice_production/uploads/upload/image/10332/direct/1742354275616/ANALOG%20INPUTS%20EXAMPLE.cxp

 
 

 