NX/NJ to CompactLogix using CIP Explicit Messages

Updated April 13, 2023

Introduction

This document shows the basic steps to connect the Omron NJ/NX controller to Rockwell CompactLogix /ControlLogix controllers via explicit messages. The guide will assume that the hardware installation is complete. This guide covers the connection to the Rockwell CompactLogix PLC specifically and for more information on CIP please see this article.

Set the IP address of both devices as shown below:

Parameter Adjustment NJ/NX Series CompactLogix
IP address 192.168.250.1 192.168.250.2
Subnet Mask 255.255.255.0 255.255.255.0


Delete

Info

Different procedures such as variable creation, program transfer, variable monitoring, etc. are omitted from this guide. Refer to the manuals or contact your device manufacturer.

Configure NX/NJ

  1. Open a new project and specify the type of driver to use, it is advisable to add comments that allow us to clearly identify the operation of that program.
  2. As a second step, set the IP and subnet mask in the "Built in EtherNet/IP Port settings" found in the Multiview Explorer.
Delete

Configure CompactLogix

  1. Open a new project and specify the type of driver to use, check the revision number of the device to be connected.
  2. Set the IP address of the device.Using the option with RSlogix 5000,look in the"Controller Organizer"window for the option "1769-L35EEthernetPortLocalENB",from here you can set the IP address and the Subnet mask, as shown in the following figure:
Delete

UCMM Read

The CIPUCMMRead statement uses an explicit UCMM message to read the value of a variable from another controller in the specified CIP network.

Parameter Description
Execute A preferably diff-up trigger signal used to execute the CIPUCMMRead command.
Timeout Specifies the timeout. If a response does not return within the timeout, it is assumed that communications have failed. The timeout increments with a 0.1 second resolution, and it uses variables of unsigned integer type (UINT), example: UINT#20 = 2 seconds of timeout.
RoutePath This is the network path used to reach the CompactLogix/ControlLogix CPU. It must be a String value, either as a constant or as a Tag, example: '02\192.168.250.2\01\#00'
SrcDat The name of the tag that will be read from the CompactLogix/ControlLogix CPU. This parameter uses constants or variables of type String to contain the name.
Size If "SrcDat" is an array, you must specify the number of items to read. If "SrcDat" is not an array, always specify 1 in this parameter. If the value of "Size" is 0, nothing is read regardless of whether "SrcDat" is an array or not. "Size" uses variables of unsigned integer type (UINT ), example: UINT#1 = 1 data to read.
DstDat Name of the Omron tag or tag, where the read data will be stored, including the initial index number (when arrays are used), the type of data used for this parameter is "ANY", that is, any type of data, including enumerations, arrays, structures, members of structures or unions.
RcvSize When the read operation is complete , the number of bytes read in this parameter is saved. A maximum of 496 bytes of data can be read.

Example - Single Variable

NX/NJ

CompactLogix

Delete

Example - Array

NX/NJ

CompactLogix

Delete
Delete

UCMM Write

The CIPUCMMWrite statement uses an explicit UCMM message to write the value of a variable to another controller in the specified CIP network.


Parameter Description
Execute A preferably diff-up trigger signal used to execute the CIPUCMMRead command.
TimeOut Specifies the timeout. If a response does not return within the timeout, it is assumed that communications have failed. The timeout increments with a 0.1 second resolution, and it uses variables of unsigned integer type (UINT), example: UINT#20 = 2 seconds of timeout.
RoutePath This is the network path used to reach the CompactLogix/ControlLogix CPU. It must be a String value, either as a constant or as a Tag, example: '02\192.168.250.2\01\#00'
DstDat Name of the tag or tag of the CPU CompactLogix/ControlLogix, where the read data will be saved, including the initial index number (when using arrays), the data type used for this parameter is "ANY", i.e. any type of data, including enumerations, arrays, structures, members of structures, or unions.
Size If "SrcDat" is an array, you must specify the number of items to read. If "SrcDat" is not an array, always specify 1 in this parameter. If the value of "Size" is 0, nothing is read regardless of whether "SrcDat" is an array or not. "Size" uses variables of unsigned integer type (UINT ), example: UINT#1 = 1 data to read.
SrcDat Name of the tag that will be read from the Omron NJ/NX CPU and sent to the CompactLogix /ControlLogix CPU. This parameter uses constants or variables of type String to contain the name.

Example - Single Variable

NX/NJ

CompactLogix

Delete

Example - Array

NX/NJ

CompactLogix


Delete
Delete

NJ_NX - Explicit Messages.smc2

NJ_NX_Explicit_Messages.ACD