Quickstart Guide: Omron GI-S Module Configuration with Rockwell Safety Logix

Updated May 21, 2025

Solution Overview

This guide provides step-by-step instructions for:

  • Configuring a new Omron GI-S module
  • Mapping the module into a Rockwell PLC I/O tree
  • Reconfiguring an already commissioned module

Hardware Used

  • Windows PC
  • Ethernet patch cable
  • Rockwell Safety Logix processor (e.g. Guardlogix)
  • Omron GI-SMD1624 CIP Remote I/O Module

Software Used

  • Rockwell BootP-DHCP Tool
  • Rockwell Studio 5000 Logix Designer (v24+ or preferably v32+)

Implementation

1. Configuring a New (Out-of-Box) GI-S Module

a. Set Hardware Switches:

With the module powered off, set the rotary dials to:

  • Mode = 1
  • x16 = 0
  • x1 = 0

b. Prepare Network:

  • Configure your PC’s Ethernet adapter to a private subnet (e.g., 192.168.1.x, subnet mask 255.255.255.0).
  • Connect an Ethernet cable from your PC to Port 1 (RJ45) of the GI-S module.

c. Assign IP Address via BootP-DHCP Tool:

  • Power on the GI-S module.
  • Wait about 10 seconds, then launch the BootP-DHCP Tool.
  • Under Tools -> Network Settings, ensure the correct adapter is selected.
  • If the module appears in the list, double-click it.
  • Assign a static IP address, then click OK.

d. Disable BootP:

  • Click the "Disable BOOTP/DHCP" button.
  • No errors should appear if successful.
  • Power cycle the module.
  • Perform a ping test to the configured IP to confirm connectivity.
 
 

2. Mapping the GI-S Module in the PLC I/O Tree

a. Add New Module in Studio 5000:

  • In your I/O configuration (under L8xES or EN2T), right-click and select New Module.
  • If needed, install the EDS file for the GI-S module.
  • Alternatively, copy-paste the module from a known working project.

b. Configure the Module:

  • Set module name, IP address, and connection settings.
  • Safety configuration will vary by application.
     

c. Download and Run:

  • Download the configuration to the PLC.
  • Put the controller into Run mode.
  • The GI-S module should display a status of ‘Running’ when the connection is established.
 
 

3. Re-configuring an Already Commissioned GI-S Module

a. Inhibit the Module:

  • Open module Properties → Connection tab.
  • Click Inhibit Module → Apply → Yes.
  • If you see a “failed to set properties” error, just cancel and reopen the dialog — the module should still be inhibited.

b. Reset Ownership:

  • Go to Properties → Safety tab.
  •  It is normal to receive a "message timeout". Click "Refresh Ownership".
  • If successful, Configuration Ownership will display as "Not Owned".

c. Set New IP Address:

  • Go to Properties → Internet Protocol tab.
  • Enter the new IP address, then click Set → Yes.

d. Re-establish Connection:

  • Go offline in Studio 5000, update the module's IP address in the General dialogue.
  • Uninhibit the module.
  • Download to the PLC.
  • The module should reconnect and return to a ‘Running’ state.
 
 

 

 

 

 