Step by Step Guide - NX-SL3300 + Estop using Sysmac Studio

Updated June 02, 2022

Introduction

The purpose of this document is to demonstrate how to connect and configure Estop using NX-SL3300 and NJ PLC. 

Pre-Requisites

The programmer should have very good understanding of Sysmac Studio programming environment

Further Reading

Delete

Please refer to these Precautions and Terms and Conditions‍ which relate to the information and program samples provided before proceeding

Procedure

Step1

Adding NX-ECC coupler in Sysmac

Double click EtherCAT and add ECC coupler by dragging it from Toolbox


Step 2

Add safety controller and IOs

Double click Node 1 NX-ECC under EtherCAT and drag all the required hardware from the toolbox list including SL3300 (mandatory) ,SID800 (mandatory), SIH400, SOD400, ID3317, OD3256

Step 3

Creating safety variable

Go to the new_SafetyCPU and select I/O Map. Provide the variable name for Si00 and Si01 as EstopButton and ResetSwitch01 respectively.

Step 4

Configuring Safety Device

Double click Parameters under safety I/O – NX-SID800. Drag Emergency Estop Switch for single channel from Toolbox to Sio0. Drag Reset Switch with Test Pulse from Input Device: Standard Input Device (Toolbox) 

Step 5

Creating Estop Function block

Double click on Program0 under safety controller. Drag SF_EmergencyStop from Toolbox to safety rung 1.

Step 6

Define variables

Activate-True

S_EStopIn : EstopButton

S_StartReset:True

S_AutoReset : False

Reset : ResetSwitch01

S_EStopOut: SafetyRelayOut

SafetyRelayOut is a safebool variable

Step 7

Go online and transfer the program to verify

For safety program you can debug by going online and clicking debug icon




End of step by step guide